Number of inputs |
4 |
Power supply |
via the K-bus |
Signal voltage |
-10…+10 V |
Technology |
single-ended |
Internal resistance |
> 130 kΩ |
Common-mode voltage UCM |
– |
Conversion time |
~ 2 ms |
Resolution |
12 bit (for 0…10 V range: resolution 11 bit) |
Measurement error/ uncertainty |
< ±0.3 % (relative to full scale value) |
Electrical isolation |
500 V (K-bus/signal voltage) |
Current consumption power contacts |
– |
Current consumption K-bus |
typ. 100 mA |
Bit width in the process image |
input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Configuration |
no address or configuration setting |
Special features |
– |
Weight |
approx. 75 g |
Operating/storage temperature |
-25…+60 °C/-40…+85 °C |
Relative humidity |
95 %, no condensation |
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. |
IP20/variable |
Approvals/markings |
CE, UL, ATEX, IECEx, DNV GL |
Pluggable wiring |
for all KSxxxx Bus Terminals |
Ex marking |
ATEX:
II 3 G Ex nA IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc |